Logo del repository
  1. Home
 
Opzioni

Prediction of lightning impulse voltage induced breakdown in vacuum interrupters

N. Marconato
•
A. De Lorenzi
•
N. Pilan
altro
N. Wenzel
2017
  • journal article

Periodico
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION
Abstract
A concept to predict the Lightning Impulse Voltage (LIV) breakdown probability of medium voltage Vacuum Interrupter (VI) tubes has been developed and tested for the first time employing the Voltage Holding Prediction Model (VHPM) originally formulated at Consorzio RFX. The VHPM is capable to calculate the Weibull breakdown probability curve of any multi-electrode multi-voltage system insulated in vacuum under dc voltage. Even though the possibility to employ the VHPM in the prediction of voltage breakdown under LIV conditions is not straightforward, the potential benefits of the VHPM usage in VI tube technology with regard to development, design and testing at medium and high voltage levels, strongly recommend the assessment of VHPM under LIV conditions. The paper aims to describe the methodology adopted to identify experimentally the VHPM parameters to be employed in such a novel application to assess its prediction capability. The measurements have been done in the Siemens Berlin VI tube factory test stand for LIV, compliant with the IEC standard. Different vacuum tube types manufactured by Siemens were investigated. The main difficulty was to obtain, with such a test bed, voltage breakdown distributions well fitted by a Weibull Distribution - upon which the VHPM is based - primarily due to the difficulty to reach a well-defined end of the conditioning test sequence preceding the relevant voltage breakdown test sequence suitable to be analyzed by the VHPM. Nevertheless, the VHPM prediction resulted in reasonable agreement with the measured probability curves. Finally, investigating VI tubes with spiral-type Radial Magnetic Field (RMF) contacts, characterized by a geometry strongly deviating from axial 2-D symmetry, the first implementation of a full 3-D version of the VHPM has been tested. © 1994-2012 IEEE.
DOI
10.1109/TDEI.2017.006485
WOS
WOS:000427640200009
Archivio
http://hdl.handle.net/11390/1128836
info:eu-repo/semantics/altIdentifier/scopus/2-s2.0-85044090847
http://ieeexplore.ieee.org/document/8315257/
Diritti
metadata only access
Soggetti
  • Electric breakdown, E...

Scopus© citazioni
2
Data di acquisizione
Jun 7, 2022
Vedi dettagli
Web of Science© citazioni
2
Data di acquisizione
Mar 17, 2024
Visualizzazioni
4
Data di acquisizione
Apr 19, 2024
Vedi dettagli
google-scholar
Get Involved!
  • Source Code
  • Documentation
  • Slack Channel
Make it your own

DSpace-CRIS can be extensively configured to meet your needs. Decide which information need to be collected and available with fine-grained security. Start updating the theme to match your nstitution's web identity.

Need professional help?

The original creators of DSpace-CRIS at 4Science can take your project to the next level, get in touch!

Realizzato con Software DSpace-CRIS - Estensione mantenuta e ottimizzata da 4Science

  • Impostazioni dei cookie
  • Informativa sulla privacy
  • Accordo con l'utente finale
  • Invia il tuo Feedback